DC 2-5 Ton Packaged Chiller with Internal Tank & Pump

2 to 5 ton packaged chiller

Construction Features Safety Features
Environmentally Friendly R-10A ETL Listed
Low profile design Low Ambient Fan Cycling
Top Discharge Condenser Exhaust Low Pressure Refrigeration Control
Easy Access Electrical Panel High Pressure Refrigeration Control
Insulated Copper Piping Low Water Flow Safety Shut-Off
Stainless Steel Heat Exchanger Short Cycling Time Delay
Compressor Crankcase Heater Temperature Sensor Failure Protection
G-90 Galvanized Cabinet Water Inline Strainer
All Weather-Tight Components
Non-Corroding Insulated Water Tank Options for Custom Designs & Modifications
Water Level Viewing Ports Hot Gas By-Pass
Water Tank Capacity of 40 Gallons Low Pressure By-Pass
Stainless Steel Pump with Ball Valve Flooded Condenser With Receiver & Accumulator
24 Volt Digital Temperature Control Module with On/Off Switch Evaporator Heat Tape Freeze Protection
High Pressure Pump
Second Pump Connection

 

ELECTRICAL SPECIFICATIONS: DC 2-5 Ton Packaged

P/N MODELS TONS VOLTS HERTZ PH MIN CIRCUIT AMP MAX FUSE COMPRESSOR PUMP HP
RLA LRA
004837 WCDCP221 2 208/230 60 1 33.9 40 14.7 72.5 1
004286 WCDCP223 2 208/230 60 3 28.5 40 10.4 63 1
004790 WCDCP243 2 460 60 3 11.2 15 4.5 31 1
004832 WCDCP321 3 208/230 60 1 37.9 50 17.9 112 1
004833 WCDCP323 3 208/230 60 3 32.4 45 13.5 88 1
004791 WCDCP343 3 460 60 3 13.6 20 6.4 39 1
004834 WCDCP421 4 208/230 60 1 48.5 60 26.4 134 1
004723 WCDCP423 4 208/230 60 3 37.8 50 16 110 1
004792 WCDCP443 4 460 60 3 15.4 20 7.8 52 1
002441 WCDCP521 5 208/230 60 1 49.5 60 27.2 150 1
004835 WCDCP523 5 208/230 60 3 39.3 50 19 123 1
004793 WCDCP543 5 460 60 3 17.7 25 9.7 62 1
Specifications are subject to change without notice.

DIMENSIONS: DC 2-5 Ton Packaged
DC-Pack-2-5

FLOW DIAGRAM: DC 2-5 Ton Packaged With OPTIONAL EXTERNAL PROCESS PUMP
TS 2-5 Ton Packaged

 